昇洋環境科技股份有限公司
Public Sector Municipal Government Office Building

IAQ Regulatory Monitoring & Remediation for a Government Building

After public complaints of stuffy air and dizziness during extended visits, a municipal office building required an annual IAQ inspection under the Indoor Air Quality Management Act, along with remediation recommendations ahead of the next regulatory audit.

Government building IAQ monitoring
Challenge

Challenge

The 1990s-era building relied on a central HVAC system without outside-air regulation. CO₂ levels in several public-service areas exceeded the 1,000 ppm statutory limit, and open-plan layouts caused airflow short-circuiting and uneven air quality.

Approach

Our Approach

  1. 01

    Measurement of nine indicators (CO₂, CO, HCHO, TVOC, PM2.5, PM10, bacteria, fungi, etc.) per NIEA A715.13C

  2. 02

    Peak-hour sampling at 10:00 / 14:00 / 16:00 to reconstruct daily fluctuation curves

  3. 03

    Hot-wire anemometry across each service zone, producing airflow heatmaps

  4. 04

    Recommendations: new-air damper rescheduling, periodic window venting, and deployment of real-time IAQ sensors

Outcomes

Outcomes

  • Compliant with the Indoor Air Quality Act
  • CO₂ concentration reduced by 28%
  • Dead-zone remediation recommendations